Diwirya, Raihandika Putra Kusuma and Drs. Ir. Moch. Dhofir, M.T and Ir. Wijono, M.T., Ph.D. (2023) Analisis Penambahan Capacitor Bank dan Detuned Reactor Terhadap Faktor Daya dan Harmonisa pada Sistem Distribusi Comvention Hall Grand Indonesia. Sarjana thesis, Universitas Brawijaya.
Abstract
Sektor industri menggunakan energi listrik yang sangat besar dan pada umumnya memiliki beban-beban induktif yang menyerap daya aktif dan daya reaktif yang cukup besar. Beban-beban induktif seperti motor, trasnformator dan las listrik memiliki komponen induktor untuk magnetisasi. Magnetisasi akan menyerap daya reaktif yang akan menyebabkan peningkatan pada rugi-rugi energi sehingga faktor daya menurun pada sistem jaringan. Maka dari itu capacitor bank sering digunakan untuk memperbaiki factor daya. Namun, penggunaan capacitor bank pada jaringan yang mengandung harmonisa, dapat menyebabkan kenaikan nilai harmonisa akibat fenomena resonansi paralel yang terjadi. Sehingga detuned reactor sering digunakan untuk mencegah kenaikan harmonisa akibat penggunaan capacitor bank. Pada penelitian ini akan dilakukan analisis penambahan capacitor bank dan detuned reactor pada jaringan Convention Hall Grand Indonesia dengan metode pemasangan global compensation dan group compensation. Pada hasil penelitian ini, Saat capacitor bank capacitor bank terpasang faktor daya jaringan dapat diperbaiki baik menggunakan metode pemasangan global compensation dan group compensation mencapai nilai 95%. Penggunaan capacitor bank pada jaringan memberikan dampak kenaikan harmonisa pada jaringan dengan rata-rata kenaikan pada setiap panel mencapai 83% pada pemasangan menggunakan metode global compensation dan 136% pada saat pemasangan capactior bank menggunakan metode group compensation. Detuned reactor ditambahkan pada jaringan dengan dipasang seri terhadap kapasitor. Hasil penelitian ini menunjukkan baik dengan metode pemasangan global compensation ataupun group compensation kenaikan harmonisa jaringan dapat dihindari dan bahkan dapat diredam. Hasil akhir nilai harmonisa jaringan mengalami rata-rata penurunan pada setiap panel mencapai 51% terhadap nilai harmonisa pada kondisi eksisting pada saat menggunakan metode pemasangan global compensation dan 47% saat pemasangan dengan metode group compensation.
English Abstract
The industrial sector uses very large amounts of electrical energy and generally has inductive loads that absorb quite high active and reactive power. Inductive loads such as motors, transformers and electric welding machines have inductance components for magnetization. Magnetization in the network system will absorb reactive power which will increase energy losses so that the power factor decreases. Therefore, capacitor banks are often used to improve the power factor. However, the use of capacitor banks in networks that contain harmonics can cause an increase in harmonic values due to the parallel resonance. So detuned reactors are often used to prevent the increase in harmonics due to the use of capacitor banks. In this research, an analysis of the addition of capacitor banks and detuned reactors to the network will be carried out using the global compensation and group compensation installation method. The results of this researc are that, when the capacitor bank capacitor bank is installed, the network power factor can be improved using both global compensation and group compensation reaching a value of 95%. The use of capacitor banks in the network increas harmonics to an average 83% when using the global compensation and 136% when using the group compensation. A detuned reactor is installed to the network in series with a capacitor. The results of this research show that by using global compensation or group compensation methods, increases of network harmonics can be avoided, and can even be reduced. The final result shows that the harmonic in each panel decrease up to 51% when using the global compensation installation method, and 47% when installing using the group compensation method compared to the harmonic value in existing conditions.
Item Type: | Thesis (Sarjana) |
---|---|
Identification Number: | 052307 |
Uncontrolled Keywords: | Faktor Daya, Harmonisa, Capcitor Bank, Detuned Reactor, Power Factor, Harmonics, Capcitor Bank, Detuned Reactor. |
Divisions: | Fakultas Teknik > Teknik Elektro |
Depositing User: | Zainul Mustofa |
Date Deposited: | 18 Jan 2024 07:07 |
Last Modified: | 18 Jan 2024 07:07 |
URI: | http://repository.ub.ac.id/id/eprint/212081 |
Text (DALAM MASA EMBARGO)
Raihandika Putra.pdf Restricted to Registered users only until 31 December 2025. Download (6MB) |
Actions (login required)
View Item |