Nur Alifah, Zalfa and Fajri Anugroho,, STP, M. Agr., Ph. D and Satwika Desantina M.,, ST, MT. (2023) Evaluasi Kinerja Unit Instalasi Pengolahan Air Limbah (IPAL) Domestik Dengan Studi Kasus Di PT United Tractors, Tbk. Sarjana thesis, Universitas Brawijaya.
Abstract
PT United Tractors, Tbk, merupakan anak perusahaan PT Astra International, Tbk. Yang memiliki pengolahan air limbah domestik atau Sewage Treatment Plant (STP) dengan lima jenis pengolahan, yaitu comminutor, bak aerasi, bak sedimentasi, bak klorinasi, dan filter. Jumlah karyawan saat ini berjumlah 100 orang dengan 50 orang tamu setiap harinya dan IPAL yang ada di PT United Tractors, Tbk, sudah lama berjalan namun hingga sekarang belum pernah diadakannya evaluasi untuk mengkaji kinerja proses unit IPAL. Maka dari itu, evaluasi IPAL dibutuhkan untuk memastikan kinerja IPAL yang ada sudah berjalan optimal dan sesuai dengan standar. Tujuan peneliti adalah untuk menginventarisasi air limbah dan mengevaluasi kinerja IPAL serta merekomendasikan program peningkatan kinerja dalam menurunkan beban pencemar.Penelitian dilakukan pada bulan Januari 2023 hingga Maret 2023. Evaluasi kinerja IPAL akan didasarkan pada inventarisasi sumber air limbah, evaluasi inlet air limbah, evaluasi proses pengolahan, dan evaluasi outlet air limbah. Sampling dilakukan dengan metode grab sampling, dan dilakukan pengujian karakteristik melalui uji laboratorium dan selanjutnya akan dilakukan perhitungan kinerja untuk mengevaluasi IPAL. Perhitungan kinerja akan dibandingkan dengan referensi standar desain unit comminutor, bak aerasi, bak sedimentasi, bak klorinasi, dan filter. Parameter yang dijadikan acuan adalah pH, BOD, COD, TSS, amonia, minyak dan lemak, total coliform, dan debit sesuai dengan baku mutu yang berlaku. Hasil penelitian yang diperoleh yaitu debit rata-rata sebesar 4,1 m iv 3 /hari dan debit puncak sebesar 13,69 m 3 /hari. Pengolahan bak aerasi memiliki efisiensi sebesar -140% pada parameter TSS, -27,8% pada parameter COD, -25,8% pada parameter BOD. Selanjutnya efisiensi removal pada bak sedimentasi sebesar 78,7% pada parameter TSS, 83,4% pada parameter COD, dan 81,25% pada parameter BOD. Efisiensi removal pada bak klorinasi sebesar 45,8% pada parameter TSS, 5,37% pada parameter amonia 5,8% dan sebesar 120% pada parameter total coliform. Terakhir adalah unit filtrasi memiliki efiensi removal sebesar 92,3% pada parameter TSS, 97,7% pada parameter amonia, 0%, 66,1% pada parameter BOD, dan 100% pada parameter total coliform. Efisiensi removal pengolahan instalasi dari awal hingga akhir cukup baik yaitu sebesar 97,8% pada parameter TSS, 97,8% pada parameter amonia, pada parameter minyak dan lemak sebesar 0%, 92,8% pada parameter COD, 91,9% pada parameter BOD, dan 100% pada parameter total coliform. Secara keseluruhan pengolahan pada IPAL domestik PT United Tractors, Tbk sudah berjalan dengan baik dan sesuai dengan Peraturan Menteri Lingkungan Hidup No. 68 tahun 2016. Namun pada bak pengolahan yang ada memiliki ketidaksesuaian di HRT bak yang dikarenakan debit yang masuk masih terlalu kecil jika dibandingkan dengan dimensi aktual IPAL. Oleh karena itu, diperlukan penyesuaian desain dengan debit aktual pada unit aerasi, sedimentasi dan klorinasi. Dilakukan penambahan bak ekualisasi untuk mengatasi fluktuasi debit dan penambahan unit pengolahan sludge. Perlu adanya pengontrolan kadar nutrien secara berkala dan diberinya nutrient fosfor dan nitrogen pada unit bak aerasi untuk mencukupi nutrisi kebutuhan mikroorganisme. Tidak hanya itu perlu juga diadakannya pengujian breakpoint chlorination secara berkala dan maintenance backwash tangki filter yang terjadwal.
English Abstract
PT United Tractors, Tbk, is a subsidiary of PT Astra International, Tbk. Which has a domestic wastewater treatment plant or Sewage Treatment Plant (STP) with five types of treatment, namely comminutor, aeration tub, sedimentation tub, chlorination tub, and filter. The current number of employees is 100 people with 50 guests every day and the WWTP at PT United Tractors, Tbk has been running for a long time but until now there has never been an evaluation to review the performance of the STP unit process. Therefore, an STP evaluation is needed to ensure that the existing STP performance is running optimally and in accordance with standards. The aim of the researchers is to inventory wastewater and evaluate the performance of the STP and recommend a performance improvement program in reducing pollutant loads. The research was conducted from January 2023 to March 2023. Evaluation of STP performance will be based on an inventory of wastewater sources, evaluation of wastewater inlet, evaluation of the treatment process, and evaluation of the wastewater outlet. Sampling is carried out using the grab sampling method, and characteristic testing is carried out through laboratory tests and then performance calculations will be carried out to evaluate the STP. Performance calculations will be compared with standard reference designs for comminutor units, aeration tanks, sedimentation tanks, chlorination tanks and filters. The parameters used as references are pH, BOD, COD, TSS, ammonia, oil and grease, total coliform, and discharge in accordance with applicable quality standards. The research results obtained were an average debit of 4.1 m3/day and a peak discharge of 13.69 m3/day. The aeration tank treatment has an efficiency of -140% on the TSS parameter, -27.8% on the COD parameter, -25.8% on the BOD parameter. Furthermore, the removal efficiency in the sedimentation tank is 78.7% for the TSS parameter, 83.4% for the COD parameter, and 81.25% for the BOD parameter. The removal efficiency in the chlorination bath was 45.8% for the TSS parameter, 5.37% for the 5.8% ammonia parameter and -120% for the total coliform parameter. Finally, the filtration unit has a removal efficiency of 92.3% on the TSS parameter, 97.7% on the ammonia parameter, 0%, 66.1% on the BOD parameter, and 100% on the total coliform parameter. The removal efficiency of the installation process from start to finish is quite good, namely 97.8% in the TSS parameter, 97.8% in the ammonia parameter, 0% in the oil and grease parameter, 92.8% in the COD parameter, 91.9% in BOD parameters, and 100% on total coliform parameters. Overall, the processing of PT United Tractors, Tbk's domestic vi STP has been going well and in accordance with the Regulation of the Minister of Environment No. 68 of 2016. However, the existing processing tanks have a discrepancy in the HRT of the tanks because the incoming discharge is still too small when compared to the actual dimensions of the STP. Therefore, it is necessary to adjust the design with the actual discharge in the aeration, sedimentation, and chlorination units. An equalization tank was added to overcome debit fluctuations and a sludge processing unit was added. It is necessary to control nutrient levels on a regular basis and provide phosphorus and nitrogen nutrients in the aeration tank unit to meet the nutritional needs of microorganisms. Not only that, it is also necessary to hold periodic breakpoint chlorination tests and scheduled filter tank backwash maintenance.
Item Type: | Thesis (Sarjana) |
---|---|
Identification Number: | 052310 |
Uncontrolled Keywords: | Air Limbah Domestik, Evaluasi, IPAL Domestic Wastewater, Evaluation, STP |
Divisions: | Fakultas Teknologi Pertanian > Keteknikan Pertanian |
Depositing User: | Unnamed user with username verry |
Date Deposited: | 15 Jan 2024 07:45 |
Last Modified: | 15 Jan 2024 07:45 |
URI: | http://repository.ub.ac.id/id/eprint/210361 |
Text (Dalam Masa Embargo)
NUR ALIFAH ZALFA.pdf Restricted to Registered users only until 31 December 2025. Download (17MB) |
Actions (login required)
View Item |