Analisis Kondisi Transformator Utama PT. PLN (Persero) UPK Tarahan Lampung Berdasarkan Hasil Uji DGA (Dissolved Gas Analysis),

Ramadhan, Bagus and Drs. Ir. Moch. Dhofir, M.T. and Tri Nurwati, S.T., M.T. (2023) Analisis Kondisi Transformator Utama PT. PLN (Persero) UPK Tarahan Lampung Berdasarkan Hasil Uji DGA (Dissolved Gas Analysis),. Sarjana thesis, Universitas Brawijaya.

Abstract

Kementerian Energi dan Sumber Daya Mineral (ESDM) mencatat bahwa konsumsi listrik Indonesia pada periode 2021 mencapai 1.123 kWh per kapita, dimana angka tersebut mengalami kenaikan dari konsumsi 2020 yang hanya mencapai 1.089 kWh per kapita. Menurut data SLD Sumatera, UIP3BS memiliki tiga sub sistem pengatur beban, yaitu UPB Sumatera Bagian Selatan, UPB Sumatera Bagian Tengah, dan UPB Sumatera Bagian Utara dengan jumlah gardu induk 202 unit dan transformator berjumlah 402 unit / 22.594 MVA. Berdasarkan data tersebut, mengetahui kondisi transformator dan melakukan tindakan pemeliharaan yang tepat terhadap transformator sangat diperlukan. Oleh sebab itu, penelitian ini bertujuan untuk mengkaji kondisi transformator utama pada unit 4 di PT. PLN (Persero) UPK Tarahan Lampung berdasarkan hasil pengujian DGA (Dissolved Gas Analysis). Pengujian DGA berfungsi untuk memberikan informasi terkait kondisi pada transformator sehingga dapat melakukan tindakan pemeliharaan yang tepat. Pada penelitian ini dilakukan beberapa proses, yaitu dengan pengambilan data hasil pengujian DGA berupa kadar nilai gas H2, CH4, CO, CO2, C2H4, C2H6, C2H2 yang terlarut dalam minyak transformator utama pada unit 4 di PT. PLN (Persero) UPK Tarahan. Kemudian dilakukan analisis hasil uji DGA menggunakan metode TDCG dengan cara menjumlahkan nilai H2, CH4, CO, C2H2, C2H4, C2H6 dalam satuan ppm dan kemudian disesuaikan dengan standar IEEE Std C57.104-2019 dan menggunakan metode Duval’s Triangle dengan menghitung nilai presentase untuk CH4, C2H2, dan C2H4 yang kemudian digambarkan pada Duval’s Triangle. Berdasarkan hasil analisis menggunakan metode TDCG (Total Dissolved Combustible Gas) dan Duval’s Triangle, kondisi transformator utama pada unit 4 PT. PLN (Persero) UPK Tarahan Lampung dalam kondisi normal. Hal tersebut juga didukung dengan nilai TDCG yang bernilai jauh dibawah 720 ppm. Oleh karena itu, kondisi ini masih dalam batas yang diizinkan untuk transformator utama unit 4 PT. PLN (Persero) UPK Tarahan beroperasi secara normal. Tindakan pemeliharaan yang direkomendasikan adalah melakukan pemantauan lebih lanjut terhadap kenaikan nilai dari setiap fault gas dan melakukan pengujian DGA dengan interval waktu yang lebih rutin.

English Abstract

The Ministry of Energy and Mineral Resources (ESDM) noted that Indonesia's electricity consumption in the 2021 period reached 1.123 kWh per capita, which experienced a slight increase from 2020 consumption which only reached 1.089 kWh per capita. According to SLD Sumatra data (2021), UIP3BS has three load control sub-systems, namely UPB Southern Sumatra, UPB Central Sumatra, and UPB North Sumatra with a total of 202 substations and 402 transformers / 22.594 MVA. Based on these data, proper maintenance measures for transformers are needed. Therefore, this study aims to examine the condition of the main transformer in unit 4 at PT. PLN (Persero) UPK Tarahan Lampung based on the results of the DGA (Dissolved Gas Analysis) test. DGA testing serves to provide information regarding the type of failure in the transformer so that it can carry out appropriate maintenance actions. In this research, several processes were carried out, namely by collecting data from the DGA test results in the form of gas levels of H2, CH4, CO, CO2, C2H4, C2H6, C2H2 which were dissolved in the main transformer oil at unit 4 PT. PLN (Persero) UPK Tarahan. Then analysis of the results of the DGA test was using the TDCG method by adding up the values of H2, CH4, CO, C2H2, C2H4, C2H6 in ppm units and then adjusting them to the IEEE Std C57.104-2019 standard and using the Duval's Triangle method by calculating the percentage value for CH4, C2H2, and C2H4 which were drawn in Duval's Triangle. Based on the results of the analysis using the TDCG (Total Dissolved Combustible Gas) and Duval's Triangle methods, the condition of the main transformer at unit 4 PT. PLN (Persero) UPK Tarahan Lampung in normal condition. This is also supported by the TDCG value which is far below 720 ppm. Therefore, this condition is still within the permissible limits for the main transformer unit 4 PT. PLN (Persero) UPK Tarahan Lampung operates normally. The recommended maintenance action is to carry out further monitoring of the increase in value of each gas fault and to perform DGA testing at more regular intervals.

Other obstract

-

Item Type: Thesis (Sarjana)
Identification Number: '0523070103
Uncontrolled Keywords: DGA, Duval’s Triangle, fault gas, TDCG, transformer
Subjects: 600 Technology (Applied sciences) > 621 Applied physics > 621.3 Electrical, magnetic, optical, communications, computer engineering; electronics, lighting > 621.38 Electronics, communications engineering > 621.381 Electronics
Divisions: Fakultas Teknik > Teknik Elektro
Depositing User: Endang Susworini
Date Deposited: 20 Jul 2023 05:52
Last Modified: 20 Jul 2023 05:52
URI: http://repository.ub.ac.id/id/eprint/201980
[thumbnail of DALAM MASA EMBARGO] Text (DALAM MASA EMBARGO)
Bagus Ramadhan.pdf
Restricted to Registered users only until 31 December 2025.

Download (3MB)

Actions (login required)

View Item View Item