Abstract

Peralatan-peralatan tenaga listrik seperti generator, transformator, kabel transmisi, pmt, dll memiliki rata- rata laju kegagalan selama berlangsungnya kehidupan peralatan tersebut (da silva & et al, 2010). Dalam Sistem kelistrikan konsep keandalan secara umum berhubungan dengan keberadaan. Keberadaan suatu peralatan cadangan sangat dibutuhkan sebagai salah satu cara alternafif untuk tetap menjaga sistem operasi walaupun peralatan utama mengalami kegagalan. Tujuan dari penelitian ini ialah untuk menentukan jumlah optimal transformator cadangan 150/20 kV dan 70/20 kV yang dibutuhkan pada PT. PLN APP Malang dengan kapasitas transformator terpasang berturut turut adalah 30 unit dan 23 unit. Dengan laju kegagalan per tahun yang didapatkan berdaasarkan IEEE C.57.11-1986 dan waktu perbaikan 1 tahun. Digunakan metode distribusi poisson berdasarkan kriteria keandalan dan MTBF serta dengan menggunakan metode nilai ekonomi dapat ditentukan jumlah optimal transformator cadangan yang dibutuhkan oleh PT PLN APP Malang. . Dari hasil perhitungan dan analisis, didapatkan bahwa jumlah optimal tranformator cadangan yang didapat berdasarkan kriteria keandalan dan MTBF sebesar 4 unit transformator cadangan 150/20 kV dan 70/20 kV dan berdasarkan perhitungan ekonomi saat terdapat 4 unit transformator memberikan hasil biaya yang lebih tinggi yaitu sebesar Rp. 6.157.555.062 pada transformator 150/20 kV dan Rp. 3.971.460.742 pada transformator 70/20 kV, jika dibandingkan saat terdapat 2 unit transformator cadangan yang merupakan biaya optimal, yaitu sebesar Rp. 3.872.395.232 pada transformator 150/20 kV dan Rp. 2.526.887.502 pada transformator 70/20 kV.

English Abstract

Electrical equipment such as generator, transformer, line transmission, circuit breaker, etc has a failure rate that varies over the life of that unit. In electrical system, reliability concepts generally related to existence of the equipment. Existence of spare equpment is very needed as an alternatif ways to keep the operating system even the main equipment fail. The purpose of this research is to compute and get the optimal number of spare transformers, 150/20 kV and 70/20 kV in PT. PLN APP Malang, with the capacity of installed transformers respectively 30 unit and 23 unit. With failure rate calculate by IEEE C57.11 and procurement rate 1 year. By using Poisson distribution method which modeled as reliabity and MTBF or average time that transformers operate till fail and also using statistical economic concept the optimal number of spare transformers which needed by PT PLN APP Malang can be determined . The results show that the calculation by reliability and MTBF criteria, the optimal number of spare transformers that needed is 4 unit in 150/20 kV and 70/20 kV. Then, by economic criteria shows that 4 unit transformers provides more expensive results, consecutively in transformers 150/20 kV and 70/20 kV

Item Type: Thesis (Sarjana)
Identification Number: SKR/FT/2017/960/051708803
Uncontrolled Keywords: Transformator, Laju kegagalan , metode distribusi poisson
Subjects: 600 Technology (Applied sciences) > 621 Applied physics > 621.3 Electrical, magnetic, optical, communications, computer engineering; electronics, lighting > 621.31 Generations, modification, storage, transmission of electric power > 621.314 Transformers
Divisions: Fakultas Teknik > Teknik Elektro
Depositing User: Budi Wahyono Wahyono
Date Deposited: 27 Sep 2017 09:54
Last Modified: 03 Nov 2020 05:29
URI: http://repository.ub.ac.id/id/eprint/2939
[thumbnail of PUJO UTOMO.pdf]
Preview
Text
PUJO UTOMO.pdf

Download (2MB) | Preview

Actions (login required)

View Item View Item