Analisis Perilaku Kontaminan Air Dalam Minyak Transformator Shel Diala B Pada Medan Listrik Homogen dan Non-Homogen

Widiastuti, Hesti Vini (2017) Analisis Perilaku Kontaminan Air Dalam Minyak Transformator Shel Diala B Pada Medan Listrik Homogen dan Non-Homogen. Sarjana thesis, Universitas Brawijaya.

Abstract

Faktor utama ketidakmurnian pada minyak transformator yaitu disebabkan oleh adanya kandungan air pada minyak transformator. Kandungan air dalam minyak transformator bisa hadir akibat proses oksidasi isolasi kertas-minyak dan penetrasi udara atmosfir ke dalam tangki. Kandungan air pada minyak transformator dapat menurunkan kekuatan dielektrik secara signifikan. Pada penelitian ini dilakukan pengujian tegangan tembus dan arus bocor minyak transformator menggunakan pembangkit tegangan tinggi AC. Cawan standar VDE 370 jarak sela 2,5 mm digunakan untuk pengujian tegangan tembus, sedangkan elektroda piring-piring dan jarum-piring digunakan untuk pengujian arus bocor minyak transformator. Pembangkit tegangan tinggi DC digunakan untuk pengujian arus konduksi minyak transformator dengan elektroda cincin pengaman jarak sela 5 mm untuk mendapatkan nilai resistivitas dan permitivitas minyak transformator. Distribusi medan listrik homogen dan tak homogen disimulasikan menggunakan Femm 4.2. Pada penelitian ini terdapat 3 kondisi yaitu minyak transformator murni, terkontaminasi air dan minyak terkontaminasi air setelah pemanasan. Pada penelitian ini didapatkan bahwa efesiensi pada elektroda piring-piring (medan homogen) dan jarum-piring (medan tak homogen) berturut-turut yaitu 100% dan 20%. Tingkat kontaminan air (0,13%) pada minyak transformator tegangan tembus menurun secara signifikan berturut-turut yaitu 23,98 kV dan 2,79 kV. Arus bocor minyak transformator dalam keadaan murni pada susunan elektroda piring-piring (medan homogen) dan elektroda jarum-piring (medan tak homogen) berturut-turut yaitu 35,4 μA dan 26,73 μA pada tegangan 30 kV jarak sela 20 mm. Pada tingkat kontaminan air (0,1%) dalam minyak transformator arus bocor naik secara signifikan pada susunan elektroda piring-piring dan elektroda jarum-piring berturut-turut yaitu 50,33 μA dan 39,87 μA dengan tegangan dan jarak sela yang sama.

English Abstract

The main factor of impurities in the oil of a transformer that is caused by the presence of moisture content in transformer oil. Moisture content in transformer oil can be present due to the oxidation process of the paper-oil insulation and air penetration into the atmosphere in the tank. Moisture content in transformer oil dielectric strength may decrease significantly. This research was conducted at the test voltage of translucent oil and the current transformer oil leaked using high voltage ac generator. The cup standard VDE 370 2,5 mm used for voltage testing is translucent, while the electrode plates and electrode needle-plates for testing current transformer oil leaked. High voltage DC generator used for testing current conduction oil transformer with a safety ring electrode distance broke in 5 mm to get the value of resistivity and permittivity of the transformer oil. Electric field distribution is not homogeneous and homogeneous simulated using Femm 4.2. In this study there are three conditions, namely the pure transformer oil, contaminated water and oil contaminated water after warming up On this research obtained that the peasants on the electrode plates (homogeneous field) and the needle plate (not-homogeneous field) consecutive 100% and 36.04%. The level of water contaminants (0.13%) on transformer oil breakdown voltage lowering significantly consecutive 23.98 kV and kV 2.79. Current transformer oil leaked in a homogeneous field and not-homogeneous consecutive 35.4 μA and 26.73 μA at 30 kV voltage interrupted distance 20 mm. The level of water contaminants (0.1%) on transformer oil leak flow significantly raise consecutive 50.33 μA and 39.87 μA with voltage and the distance the same sidelines

Item Type: Thesis (Sarjana)
Identification Number: SKR/FT/2017/505/051705997
Uncontrolled Keywords: Minyak Transformator, Kegagalan Isolasi Cair, Arus bocor, Tegangan Tembus, FEMM
Subjects: 600 Technology (Applied sciences) > 621 Applied physics > 621.3 Electrical, magnetic, optical, communications, computer engineering; electronics, lighting > 621.31 Generations, modification, storage, transmission of electric power > 621.314 Transformers
Divisions: Fakultas Teknik > Teknik Elektro
Depositing User: Budi Wahyono Wahyono
Date Deposited: 06 Sep 2017 06:42
Last Modified: 07 Dec 2020 06:52
URI: http://repository.ub.ac.id/id/eprint/2146
[thumbnail of HESTI VINI WIDIASTUTI.pdf] Text
HESTI VINI WIDIASTUTI.pdf

Download (4MB)

Actions (login required)

View Item View Item